Configuring a Network

10-7

10.2 Configuring Parameters for DeviceNet

These parameters are specific to the DeviceNet network. For more information, see
the DeviceNet Network Communication manual (HE-FP3).

DEVNET

POLL

MSG

TYPE

(P.913)

Selects which
predefined set of data
will be part of the
DeviceNet poll
connection
command/response
messages.

Parameter Range:

CONTROL

ONLY

CONTROL

+

CONFIG

Default Setting:

CONTROL

ONLY

Parameter Type:

Configurable

OIM Menu Path(s):

Network Communications

If the AutoMax network is being used, this parameter has no effect.

CONTROL

ONLY

: The smaller amount of data transmitted in the

CONTROL

ONLY

poll

message type allows greater network density and performance.

CONTROL

+

CONFIG

: The larger amount of data transmitted in the

CONTROL

+

CONFIG

poll message type allows some degree of drive configuration but decreases the
network scan rate.

NETWORK

BAUD

RATE

(P.912)

Sets the baud rate for
the DeviceNet
Interface kit. Entering
a value of 0.0 Kbaud
disables DeviceNet
network
communication.

Parameter Range:

0.0 Kbaud
125.0 Kbaud
250.0 Kbaud
500.0 Kbaud

Default Setting:

0.0 Kbaud

Parameter Type:

Configurable

OIM Menu Path(s):

Network Communications

The baud rate for the AutoMax network is not adjustable. If AutoMax network is
being used, this parameter has no effect.