Configuring Parameters for the I/O Expansion Kit

11-11

11.5 Configuring the Frequency Output

The I/O Expansion kit has one unipolar frequency output. The output is unfiltered. The
full scale value (

FSV

) is based on the selected parameter group: load, speed, voltage,

power, field, or other.

The frequency output is read every 5msec when

FEEDBACK

SELECT

(P.200) is set to

DC

TACH

,

PULSE

TACH

, or

AC

TACH

. It is read every 10msec when

FEEDBACK

SELECT

(P.200)

is set to

ARMATURE

VOLT

.

FREQ

IN

ZERO

(P.423)

Specifies the
minimum input
frequency. This is the
frequency that
corresponds to zero.

Parameter Range:

2.0 to

FREQ

IN

FULL

SCALE

kHz

Default Setting:

2.0 kHz

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Frequency I/O

If the input frequency drops below the frequency specified by this parameter, the
resulting digital value remains zero (it will not go negative).

FREQ

OUT

FULL

SCALE

(P.427)

The frequency
generated when the
signal driving the
frequency output is at
full scale, as detailed
in table 11.1.

Parameter Range:

2.0 to 250.0 kHz

Default Setting:

250.0 kHz

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Frequency I/O

For example, if

FREQ

OUT

SELECT

(P.425) is set to

CML

FEEDBACK

, the

FREQ

OUT

FULL

SCALE

frequency value is output when armature current is at

MAXIMUM

CURRENT

(P.007). (

MAXIMUM

CURRENT

is used as the basis for current minor

loop scaling.)

FREQ

OUT

SELECT

(P.425)

Selects the signal
used to drive the
frequency output
(terminals 42,43, and
44 on the I/O
Expansion kit).

Parameter Range:

See table 11.1 for options.

Default Setting:

ZERO

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Frequency I/O