8-10

FlexPak 3000 DC Drive Software Reference

FLD

WEAKEN

LEAD

FREQ

(P.520)

PI

block lead

frequency of the field
control loop’s
armature voltage
regulator.

Parameter Range:

0.01 to 282.70

RAD

/

S

Default Setting:

0.50

RAD

/

S

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning

FLD

WEAKEN

PROP

GAIN

(P.519)

The proportional gain
of the field control
loop’s armature
voltage regulator.

Parameter Range:

0.01 to 128.00

Default Setting:

1.60

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning

FLD

WEAKEN

THRESHOLD

(P.518)

Sets the point at
which the field control
loop begins
regulating armature
voltage and the field
begins to weaken.

Parameter Range:

0 to 120% of

MOTOR

RATED

ARM

VOLTS

(P.009)

Default Setting:

95% of

MOTOR

RATED

ARM

VOLTS

(P.009)

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning

If

IR

compensation is used, the threshold is

FLD

WEAKEN

THRESHOLD

at rated

armature current.