FlexPak 3000 DC Drive Software Reference
FLD
WEAKEN
LEAD
FREQ
(P.520)
PI
block lead
frequency of the field
control loop’s
armature voltage
regulator.
Parameter Range:
0.01 to 282.70
RAD
/
S
Default Setting:
0.50
RAD
/
S
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Tuning
FLD
WEAKEN
PROP
GAIN
(P.519)
The proportional gain
of the field control
loop’s armature
voltage regulator.
Parameter Range:
0.01 to 128.00
Default Setting:
1.60
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Tuning
FLD
WEAKEN
THRESHOLD
(P.518)
Sets the point at
which the field control
loop begins
regulating armature
voltage and the field
begins to weaken.
Parameter Range:
0 to 120% of
MOTOR
RATED
ARM
VOLTS
(P.009)
Default Setting:
95% of
MOTOR
RATED
ARM
VOLTS
(P.009)
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Tuning
If
IR
compensation is used, the threshold is
FLD
WEAKEN
THRESHOLD
at rated
armature current.