Troubleshooting the FlexPak 3000 Drive

13-21

.

Table 13.3 – Inverting Fault Avoidance Settings

Parameter Setting

Is Drive

Regenerating

or Attempting

to Regenerate?

Drive Action

DISABLED

n/a

None.

FAULT

IMMEDIATELY

Yes

Immediately stops (coast/DB).

Generates an

INVERTING

FAULT

AVOIDED

fault (F00015).

No (drive is

motoring)

Generates an

INVERTING

FAULT

AVOIDED

alarm (A00005).

Continues normal operation on the motoring bridge until a
request to regenerate is detected.

A request to regenerate occurs when the current minor loop
reference and feedback become opposite polarity. When a request
to regenerate is detected, the drive immediately stops (coast/DB)
and generates an

INVERTING

FAULT

AVOIDED

fault (F00015).

DELAY

BEFORE

FAULT

Yes

Immediately forces the current minor loop reference to zero.

Logs an

INVERTING

FAULT

AVOIDED

alarm (A00005).

Continues operate normally for up to two seconds. The drive can
generate a motoring current as needed but will coast while a
demand for regenerative current exists.

If the demand for regenerative current persists for approximately
two seconds, the drive:

Stops (coast/DB).

Generates an

INVERTING

FAULT

AVOIDED

fault (F00015).

If the conditions that caused the alarm return to normal before
two seconds, the drive returns to normal operation (the
regenerative bridge is re-enabled) without stopping.

No (drive is

motoring)

Logs an

INVERTING

FAULT

AVOIDED

alarm.

Continues normal operation on the motoring bridge until a
request to regenerate is detected.

When a request to regenerate is detected, the drive continues
operate normally for up to two seconds. The drive can generate a
motoring current as needed but will coast while a demand for
regenerative current exists.

If the demand for regenerative current persists for approximately
two seconds, the drive:

Stops (coast/DB).

Generates an

INVERTING

FAULT

AVOIDED

fault (F00015).

If the conditions that caused the alarm return to normal before
two seconds, the drive returns to normal operation (the
regenerative bridge is re-enabled) without stopping.