8-2

FlexPak 3000 DC Drive Software Reference

8.1

Configuring Field Economy

Field economy is available if the Enhanced Field Supply kit or Field Current Regulator
kit is installed. It is not available if you are using the standard field supply.

Field economy reduces the field voltage when the motor is at rest, reducing standby
power consumption and prolongs the insulation life of the motor field windings.

When the Field Current Regulator kit is installed, the drive enters field economy when
the drive is first powered up. When the armature becomes active, the drive goes to full
field. After the drive stops, field economy becomes active after the time specified by

FIELD

ECONOMY

DELAY

(P.501). The field economy level is adjustable through

FIELD

ECONOMY

REF

(P.511).

When the Enhanced Field Supply kit is installed, the drive powers up at full field. Field
economy is fixed at 45% of AC line voltage. After the drive stops, field economy
becomes active after the time specified by

FIELD

ECONOMY

DELAY

(P.501).

FIELD

ECONOMY

ACTIVE

(P.599) indicates when field economy is active.

The field current reference for the field loop changes depending on whether or not
field economy is active. If field economy is:

Inactive:

FIELD

REF

REGISTER

(P.513) is limited and is the field current reference.

Active:

MOTOR

HOT

FLD

AMPS

(P.510) and

FIELD

ECONOMY

REF

(P.511) are multiplied

and used as the field current reference.

You can check the value of the field current reference by looking at

FIELD

REFERENCE

(P.590)

. This reference is summed with

FIELD

FEEDBACK

and fed into the field

PI

block.

If the Field Current Regulator kit is installed, you can adjust the field economy current
level using

FIELD

ECONOMY

REF

(P.511).

FIELD

ECONOMY

REF

and/or

FIELD

REF

REGISTER

(P.513) must be above

FIELD

LOSS

THRESHOLD

(P.512) to avoid field loss faults. The

field loss logic is disabled while in field economy.

!

ATTENTION: The incorrect configuration of these parameters can cause
a motor overvoltage condition. Configure

MOTOR

HOT

FLD

AMPS

(P.510)

to the motor’s nameplate value. Failure to observe this precaution can
result in bodily injury and damage to the equipment.

FIELD

ECONOMY

ACTIVE

(P.599)

Indicates the present
state of field
economy.

This parameter has
no effect if the
standard field supply
is installed.

Parameter Range:

ON

OFF

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Field - Standard/enhanced Field Supply
Field - Field Current Regulator - Field Loop Test

Points