Troubleshooting the FlexPak 3000 Drive

13-19

13.6 Setting Reversed Tachometer or Reversed Encoder

Lead Detection

The FlexPak 3000 drive includes an algorithm for detecting reversed speed feedback
wiring. The logic verifies that the difference between the speed reference and the
speed feedback is greater than the threshold set by

TACH

LEAD

FLT

THRESH

(P.227) for

the amount of time set by

TACH

LEAD

FLT

DELAY

(P.228). When the threshold is greater

than the difference for the specified delay, and the speed reference and speed
feedback are opposite in polarity, a

REVERSED

TACH

LEADS

fault is generated

(fault F00014).

Fault F00014 can also be caused by an overhauling load, improper drive tuning, or a
tachometer or encoder loss.

The tachometer lead fault parameters have default values that are set so that reversed
tachometer lead detection is effectively disabled. You must empirically determine
values for these parameters so that reversed tachometer or encoder wiring can be
detected without generating nuisance faults.

The ability to check for reversed tachometer lead faults is useful for machine
manufacturers that require their equipment to be disassembled for shipping and
reassembled and rewired at a customer site.

This option is not available for AC tachometers.

TACH

LEAD

FLT

DELAY

(P.228)

The amount of time
that parameter P.227
(

TACH

LEAD

FLT

THRESH

) must be

exceeded before a

REVERSED

TACH

LEADS

fault (F00014)

is generated.

Parameter Range:

0 to 32767 msec

Default Setting:

10000 msec

Parameter Type:

Tunable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

TACH

LEAD

FLT

THRESH

(P.227)

The threshold after
which a

REVERSED

TACH

LEADS

fault

(F00014) is
generated.

Parameter Range:

0.0 to 250.0% of

TOP

SPEED

Default Setting:

200.0%

Parameter Type:

Tunable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

A

REVERSED

TACH

LEADS

fault is generated if the difference between the speed

reference and speed feedback is greater than this value for at least the amount of
time set by

TACH

LEAD

FLT

DELAY

.