Configuring the Outer Control Loop

9-5

OCL

REFERENCE

(P.845)

The reference value
for the outer control
loop. Displayed in

OCL

user-defined

units.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Test Points

OCL

REFERENCE

SELECT

(P.800)

Selects the reference
for the outer control
loop.

Parameter Range:

REGISTER

ANALOG

IN

1

ANALOG

IN

2

FREQUENCY

IN

NETW

IN

REG

1

NETW

IN

REG

2

NETW

IN

REG

3

Default Setting:

REGISTER

Parameter Type:

Configurable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Configure

If

REGISTER

is selected, the reference is from

OCL

REF

REGISTER

(P.801).

The I/O Expansion kit must be installed to use

ANALOG

IN

1 (terminals 50 and 51 on

the I/O expansion board),

ANALOG

IN

2 (terminals 52 and 53), or

FREQUENCY

IN

(terminals 39, 40, and 41).

A communication kit must be installed to select the communication registers
(

NETW

IN

REG

1, 2, or 3). Note that the network input registers are updated only

when Control Source (P.000) is set to

NETWORK

and the network is active.

OCL

REF

RAMP

TIME

(P.802)

The ramp time for the
outer control loop
reference.

Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Tuning

Sets the minimum amount of time for the

OCL

S-curve block output to change from 0

to full scale and vice versa. If set to 0.0, the S-curve block is bypassed.

Important: If the S-curve block is bypassed, rapid speed change can result.