Configuring the Current Minor Loop

6-9

6.4

Configuring the CML Forward Path

The proportional-integral (

PI

) controller adjusts the armature firing angle,

ARMATURE

DELTA

(P.399), to compensate for any difference between the reference and the

feedback signals. When the drive is stopped, this block’s output is clamped to zero.

Proportional gain is set by

CML

PI

PROP

GAIN

(P.301). The integral time constant can be

changed by adjusting

CML

PI

LEAD

FREQUENCY

(P.302)

Drive Current Transformer Turns Ratio (Tp/Tn)

Value to Enter

1.5 HP @ 230 VAC / 3 HP @ 460 VAC

139

2 thru 7.5 HP @ 230 VAC / 5 thru 15 HP @ 460 VAC

208

10 thru 15 HP @ 230 VAC / 20 thru 30 HP @ 460 VAC

417

20 thru 30 HP @ 230 VAC / 40 thru 60 HP @ 460 VAC

833

40 thru 75 HP @ 230 VAC / 75 thru 150 HP @ 460 VAC

2000

100 thru 150 HP @ 230 VAC / 200 thru 300 HP @ 460 VAC

5230

400 to 600 HP @ 460 VAC

7770

7A

139

29A

208

55A

417

110 A

833

265 A

2000

ARMATURE

BRIDGE

POL

(P.394)

Indicates which
bridge is currently
active.

OFF

indicates

the forward bridge.

ON

indicates the

reverse bridge.

Parameter Range:

OFF

ON

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Current Minor Loop (

CML

) -

CML

Test Points