Configuring the Speed/Voltage Loop

5-17

5.6

Configuring the Speed Loop PI Block

The proportional-integral transfer function is:

where:

K

p

=

SPD

LOOP

PI

PROP

GAIN

(P.211)

ω

ld =

SPD

LOOP

PI

LEAD

FREQ

(P.212)

When

CONTROL

SOURCE

SELECT

is set to

NETWORK

, you can reset and assign initial

values to the speed loop

PI

block. This allows you to switch between current and

speed regulation without stopping the drive.

The

PI

block is reset when

SPD

LOOP

PI

RESET

is asserted. The

PI

block is also held in

reset when the drive is stopped. While reset is asserted, the output of the

PI

block is

the initial value.

The initial value is determined by

SPD

LOOP

PI

INIT

SEL

and

SPD

LOOP

PI

INIT

VAL

.

If

CONTROL

SOURCE

SELECT

is not set to

NETWORK

, the block uses an initial value of

zero (

SPD

LOOP

PI

INIT

SEL

set to

ZERO

.)

When the

PI

block reset is used, the system must be set to minimize the error between

the actual reference and the commanded reference when changing regulation
schemes to minimize bumps in regulation. For example, when changing from speed to
current regulation, the speed loop

PI

block’s initial value should be updated with the

actual armature current feedback just before the change is made. The speed
reference should be set to speed feedback before changing from current to speed
regulation.

You can pretorque the speed regulator by setting the speed loop

PI

block’s initial value

to the desired starting torque value and releasing the block from reset after starting
the drive. The initial torque will be the initial value as the drive begins to ramp to the
reference speed.

POSITIVE

CURRENT

LIM

(P.005)

Sets the highest
amount of current (%
full load amps) for the
forward bridge. Used
as a high limit for the
speed loop

PI

block

when

POS

CURRENT

LIM

SEL

(P.223) is set

to

REGISTER

.

Parameter Range:

0 to

MAXIMUM

CURRENT

(%

FLA

)

Default Setting:

150 %

FLA

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) - Speed/Voltage Loop

(

SPD

) Tuning

Current Minor Loop (

CML

) -

CML

Tuning

Quick Start

K

p

s

ω

ld

+

s

------------------