4 configuring the serial speed reference, 5 configuring the network speed reference – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 28

Advertising
background image

4-8

FlexPak 3000 DC Drive Software Reference

4.1.4 Configuring the Serial Speed Reference

CONTROL

SOURCE

SELECT

must be set to

SERIAL

(in the FlexPak 3000 drive or through

the CS3000 software) and

AUTO

/

MANUAL

must be set to

MANUAL

to use the serial

speed reference.

If you are using the serial reference from a source such as the CS3000 software, the
reference is input directly from the serial source to the speed reference ramp. The only
parameter related to the serial speed reference is

SPD

SOURCE

SELECT

OUT

(P.193).

You can use this parameter to check the reference value.

4.1.5 Configuring the Network Speed Reference

CONTROL

SOURCE

SELECT

must be set to

NETWORK

to use the network speed reference.

When the control source is

NETWORK

, the drive is forced into automatic mode.

The only parameter related to the network speed reference is

SPD

SOURCE

SELECT

OUT

(P.193). You can use this parameter to check the reference value.

4.1.6 Configuring the Motor-Operated Potentiometer (MOP) Reference

The

MOP

function can be used as a manual reference for the speed loop. To use the

MOP

function:

The I/O Expansion kit must be installed.

CONTROL

SOURCE

SELECT

must be set to

TERMBLK

.

MANUAL

REF

SELECT

(P.106) must be set to

MOP

.

Switches must be attached to digital inputs 3 and 4 (terminals 63 and 64) of the I/O

Expansion kit. These inputs decrement and increment, respectively, the

MOP

OUTPUT

(P.191) value.

The

MOP

block is shown in figure 4.3.

The

MOP

output is incremented when digital input 4 (terminal 63) is

ON

and

decremented when digital input 3 (terminal 62) is

ON

.

MOP

OUTPUT

is limited between

MAXIMUM

SPEED

(P.004) and

MINIMUM

SPEED

(P.003). If both digital inputs are

ON

at the

same time, the

MOP

output remains at its present value.

MOP

ACCEL

TIME

(P.115) and

MOP

DECEL

TIME

(P.120) set the time in which the

MOP

OUTPUT

can change from zero to

TOP

SPEED

and vice versa. To prevent the S-curve

block from limiting the rate of change from the

MOP

OUTPUT

,

MOP

ACCEL

TIME

has a low

limit equal to

ACCELERATION

TIME

.

MOP

DECEL

TIME

has a low limit equal to

DECELERATION

TIME

.

To obtain a negative

MOP

reference, the reverse direction must be selected.

When

MOP

RESET

ENABLE

is

ON

, the

MOP

output goes to

MINIMUM

SPEED

at the moment

when the drive is stopped following a run or jog. If it is

OFF

, the

MOP

OUTPUT

remains at

its present level when the drive is stopped.

MOP

RESET

ENABLE

also affects the

operation of the keypad reference, even if the I/O Expansion kit is not installed.

Advertising