FlexPak 3000 DC Drive Software Reference

MOP

ACCEL

TIME

(P.115)

Minimum time in
which

MOP

OUTPUT

can change from zero
to

TOP

SPEED

.

Parameter Range:

ACCELERATION

TIME

to 300.0 seconds

Default Setting:

5.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp

MOP

DECEL

TIME

(P.120)

Minimum time in
which

MOP

OUTPUT

can change from

TOP

SPEED

to zero.

Parameter Range:

DECELERATION

TIME

to 300.0 seconds

Default Setting:

5.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp

MOP

OUTPUT

(P.191)

The output of the
motor-operated
potentiometer (

MOP

).

Parameter Range:

MINIMUM

SPEED

to

MAXIMUM

SPEED

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Drive Reference - Drive Reference Test Points

To get a negative

MOP

reference, the reverse direction must be selected.

If the I/O Expansion kit is not installed,

MOP

OUTPUT

is meaningless.

MOP

RESET

ENABLE

(P.116)

Determines if

MOP

OUTPUT

(P.191) and

the keypad reference
values reset or stay
at the present level
when the drive stops.

Parameter Range:

OFF

ON

Default Setting:

OFF

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

When

MOP

RESET

ENABLE

is set to

ON

(enabled),

MOP

OUTPUT

and the keypad

reference are reset to

MINIMUM

SPEED

(P.003) when the drive is stopped, even if the

I/O Expansion kit is not installed. If it is set to

OFF

(disabled),

MOP

OUTPUT

and the

keypad reference remain at their present levels when the drive is stopped.