Troubleshooting the FlexPak 3000 Drive

13-15

Figure 13.2 – Load SCRs Fail to Turn On

OPEN

SCR

SENSITIVITY

(P.600)

Open

SCR

diagnostic

sensitivity
adjustment.

Parameter Range:

0 to 100%

Default Setting:

50%

Parameter Type:

Tunable

OIM Menu Path(s):

Current Minor Loop (

CML

) -

SCR

Diagnostics

Unbalanced AC lines can cause load sharing differences between

SCR

s. Increase

the value of this parameter to increase the tolerance of

SCR

load sharing differences

due to unbalanced lines.

OPEN

SCR

TRIP

THRESH

(P.601)

Open

SCR

trip

threshold. Extremely
unusual load
conditions or severe
current loop
instability can cause
nuisance open

SCR

faults.

Parameter Range:

800 to 4000

Default Setting:

1600

Parameter Type:

Tunable

OIM Menu Path(s):

Current Minor Loop (

CML

) -

SCR

Diagnostics

Increasing this parameter increases the tolerance of such disturbances.