P.588), P.589), P.515) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 90: P.514)

Advertising
background image

8-6

FlexPak 3000 DC Drive Software Reference

FIELD

DELTA

(P.588)

The field firing angle
in degrees.

Parameter Range:

0 to 180

DEGREE

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Test

Points

FIELD

FEEDBACK

(P.589)

Motor field current
feedback signal after
scaling and gain.

Parameter Range:

+/-

MOTOR

HOT

FLD

AMPS

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Feedback

Scaling

Field - Field Current Regulator - Field Loop Test

Points

FIELD

PI

LEAD

FREQ

(P.515)

Lead frequency for
the field current

PI

block.

Parameter Range:

0 to 282.70

RAD

/

S

Default Setting:

1.50 rad/s

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning

FIELD

PI

PROP

GAIN

(P.514)

Proportional gain
setting for the field
current

PI

block.

Parameter Range:

0.10 to 128.00

Default Setting:

0.50

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Tuning