Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 69

Advertising
background image

Configuring the Speed/Voltage Loop

5-21

UNDERWIND

ENABLE

Setting this bit to 1
enables two inverter
blocks that permit
underwind operation.

Setting this bit to 0
disables the two
inverter blocks and
permits overwind
operation.

Parameter Range:

0 =

DISABLED

(overwind)

1 =

ENABLED

(underwind)

Default Setting:

0

Parameter Type:

Configurable

OIM Menu Path(s):

This parameter is only available over the network. It
cannot be viewed through the

OIM

.

Refer to the appropriate network communication manual for register map
assignments.

To use this register,

CONTROL

SOURCE

SELECT

must be set to

NETWORK

and

NETW

REGISTER

MAP

SEL

(P.914) must be set to

ALTERNATE

.

The inverters are located in the speed loop feedback path (see figure 5.1) and the
current minor loop reference path (see figure 6.1).

If

CONTROL

SOURCE

SELECT

is changed from

NETWORK

to any other control source,

the

UNDERWIND

ENABLE

bit is set to the default of

DISABLED

. If the setting was

ENABLED

, the motor can rotate in the opposite direction when the drive is restarted

with a control source other than the network.

!

ATTENTION: When

CONTROL

SOURCE

SELECT

is changed from

NETWORK

to another value,

UNDERWIND

ENABLE

is forced to

DISABLED

. This could

cause the motor to rotate in the opposite direction than it did under
network control. The active speed reference should be set to zero before
starting the drive from the new control source. Slowly increase the speed
reference until the proper rotation direction can be determined. If it is
incorrect, change the setting of the

FORWARD

/

REVERSE

input. The active

speed reference is based on the new control source and the auto or
manual setting. Failure to observe this precaution could result in severe
bodily injury or loss of life.