4-4

FlexPak 3000 DC Drive Software Reference

4.1.1 Configuring the Keypad (OIM) Speed Reference

CONTROL

SOURCE

SELECT

must be set to

KEYPAD

to use the keypad reference. When

manual mode is selected, you enter the speed reference manually through the

OIM

.

See the

OIM

manual for information on setting the speed reference through the

OIM

.

The keypad reference cannot be configured to less than

MINIMUM

SPEED

(P.003) or

greater than

MAXIMUM

SPEED

(P.004). The default value of the keypad reference is

MINIMUM

SPEED

(P.003).

4.1.2 Configuring the Analog Auto Reference

CONTROL

SOURCE

SELECT

must be set to

TERMBLK

,

SERIAL

, or

KEYPAD

to use the analog

auto input as a speed reference. When you use this speed reference, the signal is the
analog auto reference from terminals 19(+) and 20(–) of the Regulator board. Note
that this input can also be used as a current reference to the current minor loop.

You must specify the type of signal that is at terminals 19 and 20 by setting

ANLG

AUTO

SIGNAL

TYPE

(P.100) and jumpers J10 and J12 on the Regulator board. The settings of

ANLG

AUTO

SIGNAL

TYPE

(P.100) and the jumpers must be the same. See the hardware

manual for information on setting the jumpers.

The drive used the

ANLG

AUTO

GAIN

ADJ

(P.101),

ANLG

AUTO

SIGNAL

TYPE

(P.100), and

ANLG

AUTO

ZERO

ADJ

(P.102) to scale the analog auto reference signal from terminal 19

and 20 of the Regulator board to produce the

ANALOG

AUTO

REFERENCE

(P.188) signal.

!

ATTENTION: When switching from auto to manual or from manual to
auto, the drive will ramp to the reference level provided by the new source
at the rate specified by

ACCELERATION

TIME

(P.001) or

DECELERATION

TIME

(P.002). Be aware that an abrupt speed change might occur, depending
on the new reference and the rate specified in these parameters. Failure
to observe this precaution could result in bodily injury.

ANALOG

AUTO

REFERENCE

(P.188)

The analog reference
value in auto mode.
This is the value
output by the drive
after all hardware and
software scaling.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling
Drive Reference - Test Points