3 configuring parameters for the automax network, P.911), P.914) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 114

Advertising
background image

10-8

FlexPak 3000 DC Drive Software Reference

10.3 Configuring Parameters for the AutoMax Network

These parameters are only available if the AutoMax Network Communication board is
installed. For more information on the board and parameters, see the AutoMax
Network Communication board manual (D2-3318).

AMX

NETW

REF

SELECT

(P.911)

AutoMax Network
reference selection.

Parameter Range:

DIRECT

BROADCAST

n

where n = 1 to 8

Default Setting:

DIRECT

Parameter Type:

Configurable

OIM Menu Path(s):

Network Communications

Selects whether the drive reference is from the designated register in the drop
register image or from one of the eight network broadcast registers when

CONTROL

SOURCE

SELECT

is set to

NETWORK

.

NETW

REGISTER

MAP

SEL

(P.914)

Indicates which
register map
configuration will be
used for the AutoMax
Network
Communication kit.

Parameter Range:

1 =

ORIGINAL

2 =

ALTERNATE

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

ALTERNATE

selects the new register map, which permits use of additional functions.

ORIGINAL

should be used if you need to maintain compatibility with older FlexPak

drives that do not have a selectable register map (V3.12 and earlier).