11-10

FlexPak 3000 DC Drive Software Reference

11.4 Configuring the Frequency Input

ANLG

OUT

2

SELECT

(P.421)

Selects the signal
used to drive analog
output 2 (terminals
56 and 57 on the I/O
Expansion kit).

Parameter Range:

See table 11.1 for options.

Default Setting:

ZERO

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Analog I/O

When the analog output is at its maximum value, the selected signal is at is full
scale value.

Figure 11.4 – Frequency Input Block Diagram

FREQ

IN

(P.491)

The digital value of
the frequency input
(terminals 39, 40,
and 41 on the I/O
Expansion kit).

Parameter Range:

0 to 4095

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Input/Output - Frequency I/O

FREQ

IN

is scaled between

FREQ

IN

ZERO

and

FREQ

IN

FULL

SCALE

.

FREQ

IN

is zero when the frequency at the input is less than or equal to

FREQ

IN

ZERO

. It is 4095 when the frequency equals

FREQ

IN

FULL

SCALE

.

FREQ

IN

FULL

SCALE

(P.424)

Specifies the
maximum input
frequency. This is the
frequency that
corresponds to full
scale value.

Parameter Range:

2.0 to 250.0 kHz

Default Setting:

250.0 kHz

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Frequency I/O

For example, if the frequency input will be used as the speed loop reference
(selected by

AUTO

REFERENCE

SELECT

(P.103)), this input frequency will correspond

to

TOP

SPEED

(P.011), because

TOP

SPEED

is the basis for speed loop scaling.