11-6

FlexPak 3000 DC Drive Software Reference

ANLG

IN

1

GAIN

ADJ

(P.415)

Gain adjustment for
analog input 1
(terminals 50 and 51
on the I/O Expansion
kit).

Parameter Range:

0.750 to 2.250

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Analog I/O

Adjust the gain to get full scale values from the A/D converter when the maximum
level of the applied input signal is different than that of the drive.

For example, if

ANLG

IN

1

SIG

TYPE

is set to 0-10 V, a 0-8 VDC signal produces 80%

of the drive’s full scale value. To produce the drive’s full scale value using the
0-8VDC signal, change

ANLG

IN

1

GAIN

ADJ

to 1.250 (8.0V x 1.25 = 10.0V). Gain

values less than 1.000 decrease the resolution of the analog input.

Adjust the zero point (

ANLG

IN

1

ZERO

ADJ

(P.414)) before setting gain.

ANLG

IN

1

SIG

TYPE

(P.413)

Selects the type of
signal that the drive
will expect to be
connected to analog
input 1 (terminals 50
and 51 on the I/O
Expansion kit).

Parameter Range:

0– 10 V
+/–10 V
4-20 mA
10-50 mA

Default Setting:

+/–10 V

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Analog I/O

This setting must match the setting of I/O Expansion kit jumpers J11 and J12.

If the input drops below the selected value, the drive uses the low point of the range
(for example, 0 V or 4mA).

ANLG

IN

1

ZERO

ADJ

(P.414)

Adjusts the zero point
of analog input 1
(terminals 50 and 51
on the I/O Expansion
kit) to remove any
offset that might exist
on the input.

Parameter Range:

–200 to 200

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Analog I/O

To adjust the zero point, make small changes to this parameter until

ANLG

IN

1 is

zero when the signal at terminals 50 and 51 is at its zero (0V, 4mA, or 10mA).