background image

Configuring the Speed/Voltage Loop

5-7

ANALOG

TACH

GAIN

ADJ

(P.201)

Scales the analog
tachometer feedback
signal after it has
been conditioned by
the drive hardware.
Typically, it will be
1.000.

Parameter Range:

0.750 to 1.250

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

)-Speed / Voltage Loop

(

SPD

) Feedback

Important: Adjust the zero point (

ANALOG

TACH

ZERO

ADJ

(P.202)) before

configuring gain.

ANALOG

TACH

ZERO

ADJ

(P.202)

Removes any offset
from the analog
tachometer feedback
signal.

Parameter Range:

–200 to + 200

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

)-Speed / Voltage Loop

(

SPD

) Feedback

If

ANALOG

TACH

FEEDBACK

(P.291) is not equal to zero when the drive is stopped,

adjust

ANALOG

TACH

ZERO

ADJ

up or down until

ANALOG

TACH

FEEDBACK

(P.291) is

equal to zero.

ANLG

TACH

VOLTS

/1000 (P.203)

Analog tachometer
scaling from the
tachometer
nameplate in volts
per 1000

RPM

.

Parameter Range:*

18.0 to 200.0

VOLTS

/1000

RPM

Default Setting:

18.0

VOLTS

/1000

RPM

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) – Speed/Voltage Loop

(

SPD

) Feedback

Units are volts DC for DC tachometers or volts AC

RMS

for AC tachometers.

Use of an AC tachometer requires the AC Tachometer Feedback kit.

Whenever

ANLG

TACH

VOLTS

/1000 is changed, you should check the positions of

jumpers J11 and J14 to make sure they are set as indicated by J11

ANLG

TACH

VLT

SCL

(P.792) and J14

ANLG

TACH

VLT

RNG

(P.793). The tachometer wiring might also

need to be changed. See the hardware manual for more information.

*Depending on the setting of

TOP

SPEED

(P.011), the high limit might be less than

200.0 to prevent the tachometer voltage from exceeding 250V.