Configuring the Outer Control Loop

9-1

C

HAPTER

9

Configuring the Outer Control Loop

The outer control loop (

OCL

) is typically used to provide dancer position or tension

control in a web processing system. The

OCL

trims the speed/voltage loop reference

signal. The block diagram for the

OCL

is shown in figure 9.1.

The

OCL

can be configured as a:

Type 1 position regulator, which uses proportional-only control in the forward path.

Type 2 position regulator, which uses proportional-plus-integral control to reduce
steady state error to zero.

Type 3 position regulator, which inputs the

OCL

output directly into the current minor

loop.

Other

OCL

schemes.

To configure the

OCL

as a type 1 position regulator, set the lead break frequency (

OCL

PI

LEAD

FREQ

(P.809)) equal to zero (this sets the

PI

block to proportional only).

To configure the

OCL

as a type 2 position regulator, set the lead break frequency (

OCL

PI

LEAD

FREQ

(P.809)) to a non-zero value.

When enabled, the

OCL

executes every 20 msec.

Important: Scaling units of some

OCL

parameters are not predefined and must be set

by you. See the

OIM

manual to create

OCL

user-defined units.

Figure 9.1 – Outer Control Loop Block Diagram

OCL REF REGISTER

*REGISTER

ANALOG IN 1

ANALOG IN 2

FREQUENCY IN

NETW IN REG 1, 2, 3

From Network

(OCL REFERENCE)

{

OCL

REFERENCE

SELECT

OCL FEEDBACK

SELECT

(OCL RAMP

OUTPUT)

OCL REF

ROUNDING

S-CURVE

OCL REF

RAMP TIME

OCL

LEADLAG

SELECT

output of OCL

enable logic

SMOOTHING

RST\

ACC

DEC

INITV

+

output of OCL

enable logic

OCL PI

PROP GAIN

OCL PI
POSITIVE LIMIT

OCL PI

LEAD FREQ

OCL PI
NEGATIVE LIMIT

KP

HI

WLD

LO

RST\

INITV

PI

GAIN

MUL

OCL TRIM RANGE

(OCL OUTPUT)

*BYPASS

LEAD/LAG

LAG/LEAD

OCL LEADLAG
RATIO

OCL LEADLAG

LOW FREQ

(OCL FEEDBACK)

output of OCL

enable logic

INITV

L/L

WLD

RST\

RATIO

CML FEEDBACK

A N A L O G I N 1

ANALOG IN 2

(CML FEEDBACK)

8 sample average

{

*NONE

SPD LOOP OUTPUT

ANALOG AUTO REFERENCE

SPD LOOP OUTPUT

ANALOG AUTO REFERENCE

GAIN

MUL

TOP SPEED

SPEED RAMP OUTPUT

(in RPM)

ABS

DIV

ENABLED

*DISABLED

OCL PROP

TRIM SELECT

NETW IN REG 1, 2, 3

From Network

From Figure 11.2, A n a l o g
Inputs Block Diagram

From Figure 11.2, A n a l o g
Inputs Block Diagram a n d
Figure 11.4, F r e q u e n c y
Input Block Diagram

To Figure 4.7,

S p e e d R e f e r e n c e
M o d e S e l e c t
B l o c k D i a g r a m

To Figure 6.1,

C M L R e f B l o c k
D i a g r a m

Advertising