Configuring the Field Supply

8-1

C

HAPTER

8

Configuring the Field Supply

The FlexPak 3000 drive can be used with one of three types of field supplies:

Standard Field Supply: Provides field control for the standard drive. All configuration
for the standard field supply is through hardware. There are no parameters related
to the standard field supply. This supply generates a fixed field voltage and does not
provide field economy.

Optional Enhanced Field Supply: Provides electronic field trim, field economy, and
higher voltage field supplies than the standard field supply. The Enhanced Field
Supply kit must be installed to use this field supply.

Field Current Regulated Supply: Replaces the standard or enhanced field excitation
supply with a current regulated supply. It provides user-adjustable field economy,
constant horsepower operation, and user-adjustable field loss. The Field Current
Regulator kit must be installed to use this field supply.

The Field Current Regulator kit is standard for drives that are 150 to 600 HP @
460 VAC or 75 to 300HP at 230 VAC. It is optional for lower HP drives.

The parameters you will configure for the field supply depend on the supply that is
installed in your drive. You can check

FLD

CURRENT

REGULATOR

(P.586) to determine if

the Field Current Regulator kit is installed. If

FLD

CURRENT

REGULATOR

(P.586) reports

NOT

INSTALLED

, you have either the standard field supply, an Enhanced Field Supply

kit, or an incorrectly installed or failed Field Current Regulator kit. Check your drive
and installation notes to verify the type of field supply.

FLD

CURRENT

REGULATOR

(P.586)

Indicates whether or
not the Field Current
Regulator kit is
installed. If it is
installed, lists the
rating of the kit that is
installed.

Note that if “20

AMP

is displayed, a
15 amp Field Current
Regulator kit is
installed.

Parameter Range:

NOT

INSTALLED

4

AMP

10

AMP

20

AMP

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Field - Field Current Regulator
Field - Standard/enhanced Field Supply