P.607), P.649), P.605) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 131

Advertising
background image

Configuring the Drive to Use Level Detectors

12-3

LEVEL

DETECT

2

DELAY

(P.607)

The delay time in
seconds for the level
detector 2 circuit.

Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Level Detectors

Sets the amount of time between when the level detector timer is triggered and
when the output is set

ON

. If the input source signal goes below the detector’s

threshold value, the timer is immediately reset.

LEVEL

DETECT

2

OUTPUT

(P.649)

The output of level
detector 2. This
signal drives digital
output 2 (terminals
68 and 69 on the I/O
Expansion kit) if

DIG

OUT

2

SELECT

is set to

LEVEL

DETECT

2

OUTPUT

.

Parameter Range:

ON

OFF

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Input/Output - Level Detectors

ON

when the input signal selected by

LEVEL

DETECT

2

SELECT

(P.605) is greater than

or equal to

LEVEL

DETECT

2

THRESH

(P.606) for longer than

LEVEL

DETECT

2

DELAY

(P.607).

OFF

whenever the input signal is less than

LEVEL

DETECT

2

THRESH

.

LEVEL

DETECT

2

SELECT

(P.605)

Selects the signal
that drives level
detector 2.

Parameter Range:

CML

FEEDBACK

SPD

LOOP

FEEDBACK

SPD

RAMP

INPUT

TP

SPEED

RAMP

OUTPUT

SPD

SOURCE

SELECT

OUT

Default Setting:

SPD

RAMP

INPUT

TP

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Level Detectors