Configuring the Speed Reference

4-21

REVERSE

DISABLE

(P.015)

When

ON

,

REVERSE

DISABLE

does not

allow the speed
reference to drop
below zero.

When

OFF

, the speed

reference can drop
below zero and the
drive can operate in
the reverse direction.

Parameter Range:

OFF

ON

Default Setting:

OFF

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Limits
Quick Start

REVERSE

DISABLE

applies only to regenerative drives.

REVERSE

DISABLE

is forced to

ON

when:

The drive has a non-regenerative (S6) power unit.

FEEDBACK

SELECT

is set to

AC

TACH

.

FEEDBACK

SELECT

is

PULSE

TACH

and

PULSE

TACH

QUADRATURE

(P.208) is

OFF

.

S

-

CURVE

ROUNDING

(P.014)

The amount of
reference smoothing
(rounding) of the
speed loop S-curve
output.

Parameter Range:

0 to 50%

Default Setting:

0%

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp

S

-

CURVE

ROUNDING

is set as a percentage of

ACCELERATION

TIME

(P.001).

Rounding is performed at the beginning and end of a speed loop reference change.

If

TRIM

MODE

SELECT

(P.110) is set to

PROPORTIONAL

,

S

-

CURVE

ROUNDING

should be

set to 0%. If there is S-curve rounding and proportional trim, the actual trim will
interfere with the

ACCELERATION

TIME

and the

DECELERATION

TIME

and draw will not

be constant. If

TRIM

MODE

SELECT

(P.110) is set to

INCREMENTAL

,

ACCELERATION

TIME

and the

DECELERATION

TIME

are not affected.

If

S

-

CURVE

ROUNDING

is set to 0%, the speed loop performs a linear ramp function. If

it is set to 50%, the entire ramp time is smoothed: 50% at the beginning and 50% at
the end. Refer to figure 4.6.

Figure 4.6 – S-Curve Rounding