FlexPak 3000 DC Drive Software Reference

4.3.1 Configuring the Speed Reference Ramp

ACCELERATION

TIME

(P.001)

Sets the minimum
time that the selected
speed reference can
changed from zero to

TOP

SPEED

(P.011).

Parameter Range:

0.1 to 300.0 seconds

Default Setting:

5.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp
Quick Start

If

TRIM

MODE

SELECT

(P.110) is set to

PROPORTIONAL

, the actual time to accelerate

might be modified by

DRAW

PERCENTAGE

OUT

(P.196). See section 4.2, Configuring

Trim.

AUTO

MODE

MIN

BYPASS

(P.111)

Disables the

MINIMUM

SPEED

(P.003) limit

while in auto mode. If
the drive is in manual
mode, this parameter
has no effect and the

MINIMUM

SPEED

(P.003) limit cannot
be bypassed.

Parameter Range:

OFF

ON

Default Setting:

OFF

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Limits

!

ATTENTION: This drive can operate at and maintain zero speed when
this parameter is set to

ON

. The user is responsible for assuring safe

conditions for operating personnel by providing suitable guards, audible
or visual alarms, or other devices to indicate that the drive is operating
at or near zero speed. Failure to observe this precaution could result in
severe bodily injury or loss of life.