FlexPak 3000 DC Drive Software Reference

5.1

Configuring the Speed Loop Scan Time

The scan time of the speed loop can be configured using parameter P.019 (Speed
Loop Scan Time). The drive must be stopped to modify the value of this parameter.
Note that P.019 applies only to closed loop speed control using actual measured
motor velocity via tachometer or encoder-type devices.

SPD

LOOP

SCAN

TIME

(P.019)

Selects the speed
loop scan time for
closed loop
operation.

Parameter Range:

0 = 5 msec
1 = 10 msec

Default Setting:

5 msec

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters

When

FEEDBACK

SELECT

(P.200) is set to armature voltage, the active speed loop

scan time is fixed at 10 msec regardless of the setting of P.019.

When

FEEDBACK

SELECT

is changed from armature voltage to any other setting, the

active speed loop scan time is determined by the parameter setting of P.019.