4-12

FlexPak 3000 DC Drive Software Reference

DIG

IN

2 (P.496)

The state of digital
input 2 (terminal 60
on the I/O Expansion
kit).

Parameter Range:

ON

OFF

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Input/Output - Digital I/O

Digital inputs 1 and 2 (terminals 59 and 60) select which, if any, preset speed is
used as the reference for the speed/voltage control loop.

The input is

ON

when +24 VDC is applied for more than 10 msec. It is

OFF

when

0 VDC is applied.

PRESET

SPEED

1 (P.117)

PRESET

SPEED

2 (P.118)

PRESET

SPEED

3 (P.119)

These parameters
set up to three preset
speed references
when the

REGULATOR

TYPE

jumper (J15 on

the Regulator board)
is set for the
speed/voltage control
loop.

Parameter Range:

MINIMUM

SPEED

to

MAXIMUM

SPEED

(

RPM

or

user-defined units)

Default Setting:

250

RPM

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

To use these speeds,

CONTROL

SOURCE

SELECT

must be set to

TERMBLK

.

The preset speeds are selected through digital input 1 and digital input 2 on the I/O
Expansion kit, as shown in table 4.2.

If the I/O Expansion kit is not installed, the digital inputs are set to

OFF

and cannot

be changed. The selected auto or manual reference is used for the reference.

The preset speed reference passes through the same control blocks as other
speed references.