Troubleshooting the FlexPak 3000 Drive

13-13

13.3 Phase Locked Loop (PLL) Maximum Error

If your drive power is supplied by a source that cannot maintain a suitable fixed
frequency output (such as an alternator), you can adjust this parameter to prevent
faults related to line synchronization.

PLL

MAXIMUM

ERROR

(P.308)

Maximum allowable
change in line period
per AC line cycle.

Parameter Range:

2 to 1000

µ

sec

Default Setting:

2

µ

sec

Parameter Type:

Tunable

OIM Menu Path(s):

Current Minor Loop (

CML

) - Three Phase

AC Line

This parameter should only be increased when drive power is supplied by a source
that cannot maintain a suitable fixed frequency output (such as an alternator) to
prevent faults related to line synchronization.