13-22

FlexPak 3000 DC Drive Software Reference

13.8 Checking the AC Line Period and Voltage

AC

LINE

PERIOD

(P.393)

The AC line period as
measured by the drive in
microseconds. Line period =
1/line frequency in Hertz.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Current Minor Loop (

CML

) - Three Phase AC

Line

AC

LINE

VOLTAGE

(P.392)

The AC line

RMS

voltage as

measured by the drive.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Current Minor Loop (

CML

) - Three Phase AC

Line

PHASE

LOSS

DETECTION

EN

(P.609)

Enables or disables phase loss
detection.

Parameter Range:

DISABLE

ENABLE

Default Setting:

ENABLE

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (

CML

) - Three Phase AC

Line

When set to

ENABLE

, a

PHASE

LOSS

fault (F00016) is generated when the

measured AC line voltage drops below 75% of the value specified by

NOMINAL

AC

LINE

VOLTS

(P.307) for more than 2 seconds.