13-4

FlexPak 3000 DC Drive Software Reference

F00009

CONTROLLER

THERMOSTAT

TRIP

Drive thermostat indicates high temperature (>50°C)

Possible causes:

Inadequate heat sink ventilation.

Inadequate cabinet ventilation.

Heat sink fan failure.

Damaged or disconnected drive thermostat wiring.

F00010

AC

LINE

SYNCHRONIZATION

FAULT

Three-phase AC line synchronization circuit failure.

Possible causes:

Blown AC line fuse(s).

AC line frequency not within required range of 48 to 62Hz.

Excessive AC line noise or distortion.

Unstable AC line frequency. See

PLL

MAXIMUM

ERROR

(P.308).

Disconnected, loosely connected or damaged J6 ribbon cable.

F00011

OIM

COMMUNICATIONS

TIMEOUT

The Regulator board was unable to communicate with the interface
module (

OIM

or

DCM

). (See the hardware manual for a description of

regulator status

LED

s that can pinpoint whether or not the interface module

is communicating.)

Possible causes:

Disconnected, loosely connected, or damaged interface module/serial
cable.

Regulator board failure.

F00012

ARMATURE

OVER

VOLTAGE

Armature voltage exceeded 125% of

MOTOR

RATED

ARM

VOLTS

(P.009).

Possible causes:

MOTOR

RATED

ARM

VOLTS

not set properly.

Improper voltage loop tuning.

ENHANCED

FLD

VOLT

ADJ

(P.500) set too high (Enhanced Field Supply kit

only).

F00013

NETWORK

COMMUNICATION

TIMEOUT

Network communications is missing or failed to communicate with master
(

CONTROL

SOURCE

SELECT

set to

NETWORK

).

Possible causes:

NETW

CONNECT

TYPE

(P.910) was changed from

BASIC

to

FULL

.

NETW

DROP

NUMBER

(P.900) was changed.

Network option cable connections are loose or not connected.

Network option board failed or master communications failed.

Table 13.1 – Fault Codes (Continued)