Configuring the Current Minor Loop

6-3

6.2

Selecting and Conditioning CML Reference Selection

A hardware jumper, J15, configures the drive as a current/torque or speed/voltage
regulator. When J15 is set to

CURRENT

, the input signal

TORQUE

REFERENCE

(P.189) is

the

CML

reference.

TORQUE

REFERENCE

can come from an analog input, frequency

input, or a network master. When J15 is set to

SPEED

, the signal

SPD

LOOP

OUTPUT

(P.299) is the

CML

reference. The software reads the setting of hardware jumper J15

only at powerup. See the hardware manual for information on setting jumpers.

The selected

CML

reference passes through an amplitude limit block and a rate limit

block. See figure 6.1 for the block diagram.

The amplitude limit block prevents the reference signal from becoming greater than or
less than the limits selected by

CML

REF

LIMIT

SELECT

(P.311). These limits can be

either the values set by parameters

NEGATIVE

CURRENT

LIM

(P.006) and

POSITIVE

CURRENT

LIM

(P.005), or the limit values being used by the speed loop

PI

block.

The rate limit block limits the rate of change of the selected

CML

reference based on

value you input for

CML

REF

RATE

LIMIT

(P.303).

CML

REF

RATE

LIMIT

(P.303) defines the

minimum allowable time (in milliseconds) that the reference can change from zero to

MAXIMUM

CURRENT

(P.007). When the drive is stopped, the output of the rate limit block

is clamped to zero. The amplitude and rate-limited

CML

reference appears as the

output parameter

CML

REFERENCE

(P.396).

NORMALIZED

INERTIA

(P.222)

The time required to
accelerate the motor
and load inertia from
zero to motor base
speed at

MOTOR

RATED

ARM

VOLTS

(P.009) and

MOTOR

HOT

FLD

AMPS

(P.510).

Parameter Range:

0.05 to 65.20 seconds

Default Setting:

1.00 second

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed/Voltage Loop

(SPD) Tuning

This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.

CML

REF

LIMIT

SELECT

(P.311)

Selects the source for
the

CML

positive and

negative current
limits.

Parameter Range:

1 =

SPD

LOOP

PI

LIMITS

2 =

REGISTER

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

If you select

REGISTER

, the

CML

loop limits are

POSITIVE

CURRENT

LIM

(P.005) and

NEGATIVE

CURRENT

LIM

(P.006).

If you select

SPD

LOOP

PI

LIMITS

, the

CML

loop reference limits are the same as those

used by the speed loop

PI

block.