Troubleshooting the FlexPak 3000 Drive

13-7

F00065

SELF

TUNING

FAULT

Speed unstable.

Possible causes:

CML

not properly tuned before speed loop.

Tachometer or encoder feedback device connected incorrectly.

F00066

SELF

TUNING

FAULT

SELF

TUNE

STABILITY

(P.219) is too low.

Possible causes:

Specified stability is less than that calculated by

CML

self-tuning. Use 50

or more.

F00067

SELF

TUNING

FAULT

SELF

TUNE

STABILITY

(P.219) is too low.

Possible causes:

Specified stability is less than that calculated by

CML

self-tuning. Use 75

or more.

F00089 to
F00099

SELF

TUNING

FAULT

Fatal self-tuning fault occurred.

Possible cause:

Self-tuning was unable to complete. Tune manually.

F00100

MAIN

CONTACTOR

DID

NOT

OPEN

The main (

FN

) contactor did not open following a run or jog request. If a

dynamic braking kit is used, the dynamic braking auxiliary contact is wired
in series with the

FN

auxiliary contact.

Possible causes:

Disconnected, loosely connected, or damaged

FN

,

FN

auxiliary, dynamic

braking, or dynamic braking auxiliary wiring.

FN

,

FN

auxiliary, dynamic braking, or dynamic braking auxiliary contactor

failure.

Disconnected, loosely connected, or damaged main contactor or
dynamic braking control wiring (

MCR

or

DBCR

).

F00200

POWER

FAILURE

The power supply input voltage momentarily went below tolerance.

Possible causes:

AC line voltage dip.

Disconnected, loosely connected, or damaged J7 ribbon cable or power
supply input wiring

Table 13.1 – Fault Codes (Continued)

Code