6-8

FlexPak 3000 DC Drive Software Reference

The setting of

CT

TURNS

RATIO

can affect the value of

J

18

ARM

I

FB

RESISTOR

(P.395).

Check

J

18

ARM

I

FB

RESISTOR

(P.395) and the setting of the J18 jumper if you change

CT

TURNS

RATIO

.

MOTOR

RATED

ARM

AMPS

(P.008)

The rated armature
current from the
motor nameplate.

Parameter Range:

0 to 3000.0 amps

Default Setting:

8.0 amps

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (

CML

) -

CML

Feedback Scaling

Quick Start

The setting of

MOTOR

RATED

ARM

AMPS

can affect the value of

J

18

ARM

I

FB

RESISTOR

(P.395). Check

J

18

ARM

I

FB

RESISTOR

(P.395) and the setting of the J18 jumper if

you change

MOTOR

RATED

ARM

AMPS

.

!

ATTENTION: This parameter must be less than the motor rated armature
amps or drive current rating listed on the motor nameplate. If this is
configured incorrectly, overcurrent or excess heating of the motor could
result. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

CT

TURNS

RATIO

(P.010)

The drive current
transformer turns
ratio (Tp/Tn).

See Regulator board
replacement
instructions for
information on
determining the

CT

TURNS

RATIO

. This

parameter is not
restored if a Restore
Defaults is done.

Parameter Range:

139
208
417
833
2000
5230

OTHER

Default Setting:

n/a
(set at the factory based on the drive horsepower and
AC line voltage.

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (

CML

) -

CML

Feedback Scaling

!

ATTENTION: The

CT

TURNS

RATIO

parameter is used in the calculation

of the burden resistor value. Do not change this parameter from its
factory default value unless you are replacing the Regulator board.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.