Configuring the Speed Reference

4-27

JOG

OFF

DELAY

TIME

(P.121)

Specifies the
minimum delay
between removing
the jog input and
opening of the main
contactor in the drive.

Parameter Range:

0.0 to 10.0 seconds

Default Setting:

1.0 second

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Releasing the jog input will not cause the contactor to open until the speed
feedback is less than or equal to

STOP

SPEED

THRESHOLD

or until the

JOG

OFF

DELAY

TIME

is exceeded, whichever occurs last.

This delay reduces the wear on the contactor when repeatedly opening and closing
the

JOG

input in a short period of time.

JOG

RAMP

OUTPUT

(P.294)

The jog reference
value immediately
after the jog ramp
function.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Drive Reference - Drive Reference Test Points

JOG

SPEED

1 (P.012)

The operating speed
while the drive is
jogging if

DIG

IN

0

SELECT

(P.428) is set

to

JOG

SPEED

SELECT

and digital input 0
(terminal 12 on the
Regulator board) is
off.

Parameter Range:

0 to

MAXIMUM

SPEED

(

RPM

or user-defined units)

Default Setting:

250

RPM

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure
Quick Start

JOG

SPEED

2 (P.017)

The operating speed
when the drive is
jogging if

DIG

IN

0

SELECT

(P.428) is set

to

JOG

SPEED

SELECT

and digital input 0
(terminal 12 on the
Regulator board) is
on.

Parameter Range:

0 to

MAXIMUM

SPEED

(

RPM

or user-defined units)

Default Setting:

250

RPM

Parameter Type:

Tunable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)