Configuring the Outer Control Loop

9-11

OCL

LEADLAG

RATIO

(P.807)

The ratio between the
low break frequency
and high break
frequency of outer
control loop lead/lag
block.

Parameter Range:

2 to 20

Default Setting:

10

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Tuning

The settings of this parameter and the

OCL

LEADLAG

LOW

FREQ

determine the high

break frequency.

Increasing this value increases the ratio between the low and high frequencies. If

OCL

LEADLAG

SELECT

(P.805) is set to

LEAD

/

LAG

,

OCL

LEADLAG

RATIO

sets the break

frequency for lag. If

OCL

LEADLAG

SELECT

(P.805) is set to

LAG

/

LEAD

, this sets the

break frequency for lead.

OCL

LEADLAG

SELECT

(P.805)

Selects the outer
control loop as
lead/lag, lag/lead, or
bypassed.

Parameter Range:

LEAD

/

LAG

BYPASS

LAG

/

LEAD

Default Setting:

BYPASS

Parameter Type:

Tunable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Configure

OCL

TYPE

3

POSN

REG

EN

(P.814)

Selects the source of
the Current Minor
Loop reference when
the drive is
configured as a
current regulator (i.e.,
when hardware
jumper J15 is set to

CURRENT

).

Parameter Range:

DISABLED

ENABLED

Default Setting:

DISABLED

Parameter Type:

Configurable

OIM Menu Path(s):

Outer Control Loop (

OCL

) -

OCL

Configure

When set to

DISABLED

,

TORQUE

REFERENCE

(P.189) is used as the

CML

reference.

When set to

ENABLED

,

OCL

OUTPUT

(P.848) is used as the

CML

reference.