P.409), P.412) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 119

Advertising
background image

Configuring Parameters for the I/O Expansion Kit

11-3

DIG

OUT

1

SELECT

(P.409)

Selects the signal
that drives digital
output 1 (terminals
66 and 67 on the I/O
Expansion kit).

Parameter Range:

LEVEL

DETECT

1

OUTPUT

LEVEL

DETECT

2

OUTPUT

IN

CURRENT

LIMIT

DRIVE

READY

NETW

COMM

STATUS

NETW

IN

REG

1 (bit 0)

NETW

IN

REG

2 (bit 0)

NETW

IN

REG

3 (bit 0)

Default Setting:

LEVEL

DETECT

1

OUTPUT

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

LEVEL

DETECT

1 or 2

OUTPUT

: The state of the selected level detector output is

used to drive digital output 1. The signal is from the I/O Expansion kit digital
output 1 or 2. See chapter 12, Configuring the Drive to Use Level Detectors.

IN

CURRENT

LIMIT

: The armature in-current-limit signal is used to drive digital

output 1. The in-current-limit signal indicates whether or not the drive is operating
at the maximum allowable current. See

CML

REF

LIMIT

SELECT

(P.311).

DRIVE

READY

: The drive-is-ready signal is used to drive digital output 1. The

drive-is-ready signal indicates that the drive will start when the next run or jog
command is received.

NETW

COMM

STATUS

: The state of

NETW

COMM

STATUS

(P.908) is used to drive

digital output 1. See chapter 10 for description.

NETW

IN

REG

1, 2, or 3: Bit 0 of

NETW

IN

REG

1 (P.905), 2 (P.906), or 3 (P.907) is

used to drive digital output 1. A network kit must be installed to select the network
input registers. Note that the network input registers are updated only when
Control Source (P.000) is set to

NETWORK

and the network is active. See chapter

10 for description.

DIG

OUT

2

CONTACT

TYP

(P.412)

Selects whether
digital output 2
(terminals 68 and 69
on the I/O Expansion
kit) is normally open
or normally closed.

Parameter Range:

NORMAL

OPEN

NORMAL

CLOSED

Default Setting:

NORMAL

OPEN

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

If

NORMAL

OPEN

is selected, digital output 2 is open when the signal selected by

DIG

OUT

2

SELECT

(P.411) is off and closed when it is on.

If

NORMAL

CLOSED

is selected, digital output 2 is closed when the signal selected by

DIG

OUT

2

SELECT

(P.411) is off and open when it is on.

!

ATTENTION: On a power cycle or reset, the contact is held open until the
drive software powerup diagnostics are complete. Make sure this condition
does not result in a dangerous situation for your application. Failure to
observe this precaution can result in severe bodily injury or loss of life.