3

Initial Configuration

This chapter describes settings you might need to make when initially starting your
drive, including selecting a control source and changing the settings of the AC line
parameters. Before using the parameters in this chapter, perform Quick Start (see the

OIM

manual for detail).

3.1

Selecting a Control Source

The control source determines the source of drive control signals. Control signals
include drive operating signals, such as run and jog, and the drive reference.

You can select the control source on the

OIM

using the front panel key (

). See

your

OIM

manual.

CONTROL

SOURCE

(P.000)

Selects the source of
the drive control
signals.

Parameter Range:

KEYPAD

SERIAL

TERMBLK

NETWORK

Default Setting:

KEYPAD

Parameter Type:

Configurable

OIM Menu Path(s):

On

OIM

keypad:

If the drive is configured as a current (torque) regulator (jumper J15 is set to

CURRENT

), the control source can only be set to

TERMBLK

or

NETWORK

.

The possible control sources are:

KEYPAD

: Control is through the keypad.

TERMBLK

: Control is through Regulator board terminals 16 through 20. See the

hardware manual for terminal descriptions and wiring instructions.

NETWORK

: Control is through a network such as the AutoMax Network

Communication kit, DeviceNet Interface kit, or ControlNet Network
Communicaiton kit.

SERIAL

: Control is through a personal computer running the CS3000 software.