P.521), P.590), P.516) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 91

Advertising
background image

Configuring the Field Supply

8-7

FIELD

REF

SELECT

(P.521)

Selects the reference
source for the field
current regulator.

Parameter Range:

1 =

REGISTER

2 =

ANALOG

MAN

TRIM

REF

3 =

ANALOG

IN

1

4 =

ANALOG

IN

2

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

An I/O Expansion kit must be installed to select

ANALOG

IN

1 or

ANALOG

IN

2.

REGISTER

is the

FIELD

REF

REGISTER

(P.513), which can also be modified through a

network register (drop_1, register 37).

FIELD

REFERENCE

(P.590)

Field current
reference.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Test

Points

When

FIELD

ECONOMY

ACTIVE

(P.599) is

OFF

, it is the limited value of the selected

field reference.

When

FIELD

ECONOMY

ACTIVE

(P.599) is

ON

, it is the field economy reference.

FLD

FEEDBACK

GAIN

ADJ

(P.516)

Gain adjustment for
the field current
feedback.

In most cases, this
will be set for unity
gain (1.000).

Parameter Range:

0.900 to 1.100

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Feedback

Scaling