Configuring the Drive to Use Level Detectors

12-1

C

HAPTER

12

Configuring the Drive to Use

Level Detectors

The level detectors detect when the absolute value of a signal becomes greater than
or equal to a specified threshold for longer than a specified period. They can be used
as zero-speed detectors, at-speed detectors, or limit switches. They are used to drive
I/O Expansion kit digital output 1 or 2. To use the level detectors,

DIG

OUT

1

SELECT

(P.409) or

DIG

OUT

2

SELECT

(P.411) must be set to

LEVEL

DETECT

1

OUTPUT

or

LEVEL

DETECT

2

OUTPUT

. Level detector outputs can also be monitored over the AutoMax

network.

Figure 12.1 – Level Detectors Block Diagram

LEVEL

DETECT

1

DELAY

(P.604)

The delay time in
seconds for the level
detector 1 circuit.

Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Level Detectors

Sets the amount of time between when the level detector timer is triggered and
when the output is set

ON

. If the input source signal goes below the detector’s

threshold value, the timer is immediately reset.

To Figure 11.1,

Digital

Outputs Block Diagram

From Figure 5.1,

Speed Loop Block Diagram

From Figure 4.5,

Speed Reference

Ramp Block Diagram

From Figure 4.2,

Speed Reference

Source Select Block Diagram

* Default Selection