3 self-tuning parameters, P.220), P.218) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 19

Advertising
background image

Initial Configuration

3-3

3.3

Self-Tuning Parameters

See the

OIM

manual for detail on using self-tuning and the self-tuning parameters.

SELF

TUNE

BRIDGE

(P.220)

Determines the
direction the motor
shaft will rotate
during the speed loop
self-tune process by
selecting the

SCR

bridge. If the reverse
bridge will be
predominant in the
application, select

REVERSE

.

Parameter Range:

FORWARD

REVERSE

Default Setting:

FORWARD

Parameter Type:

Tunable

OIM Menu Path(s):

Current Minor Loop (

CML

) - Tuning - Self Tuning

Setup

Speed/Voltage Loop (

SPD

) - Tuning - Self Tuning

Setup

For non-regenerative (S6) drives, this is fixed to

FORWARD

.

Must be set before starting speed loop self-tuning.

SELF

TUNE

FIELD

RANGE

(P.218)

Ratio of motor top
speed to base speed.
Typical value is 1.00,
where

TOP

SPEED

(P.011) is equal to
base speed. Applies
to speed loop tuning
only.

Parameter Range:

0.90 to 5.00

Default Setting:

1.00

Parameter Type:

Tunable

OIM Menu Path(s):

Current Minor Loop (

CML

) - Tuning - Self Tuning

Setup

Speed/Voltage Loop (

SPD

) - Tuning - Self Tuning

Setup

Must be set before starting speed loop self-tuning.