P.648), P.602), P.603) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 130

Advertising
background image

12-2

FlexPak 3000 DC Drive Software Reference

LEVEL

DETECT

1

OUTPUT

(P.648)

The output of level
detector 1. This
signal drives digital
output 1 (terminals
66 and 67 on the I/O
Expansion kit) if

DIG

OUT

1

SELECT

is set to

LEVEL

DETECT

1

OUTPUT

.

Parameter Range:

ON

OFF

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Input/Output - Level Detectors

ON

when the input signal selected by

LEVEL

DETECT

1

SELECT

(P.602) is greater than

or equal to

LEVEL

DETECT

1

THRESH

(P.603) for longer than

LEVEL

DETECT

1

DELAY

(P.604).

OFF

whenever the input signal is less than

LEVEL

DETECT

1

THRESH

.

LEVEL

DETECT

1

SELECT

(P.602)

Selects the signal
that drives level
detector 1.

Parameter Range:

CML

FEEDBACK

SPD

LOOP

FEEDBACK

SPD

RAMP

INPUT

TP

SPEED

RAMP

OUTPUT

SPD

SOURCE

SELECT

OUT

Default Setting:

SPD

LOOP

FEEDBACK

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Level Detectors

LEVEL

DETECT

1

THRESH

(P.603)

The threshold for
level detector 1.

Parameter Range:*

0.1 to 100.0% or

MAXIMUM

CURRENT

Default Setting:

10.0%

Parameter Type:

Tunable

OIM Menu Path(s):

Input/Output - Level Detectors

When the absolute value of the signal driving level detector 1 is greater than or
equal to this threshold, the associated timer starts. If the input signal is less than
this threshold, the timer is immediately reset. The level detector output is set to

OFF

.

*The parameter range for the level detector is automatically rescaled for speed or
current based on the input selected by

LEVEL

DETECT

1

SELECT

(P.602). If

CML

FEEDBACK

is selected for

LEVEL

DETECT

1

SELECT

, the parameter range is 0.1 to

MAXIMUM

CURRENT

. For any other

LEVEL

DETECT

1

SELECT

settings, the parameter

range is 0.1 to 100.0%.