Configuring the Speed/Voltage Loop

5-19

SPD

LOOP

PI

LEAD

FREQ

(P.212)

Speed loop

PI

block

lead break frequency.

Parameter Range:

0.00 to 282.74

RAD

/

S

when

FEEDBACK

SELECT

(P.200) =

ARMATURE

VOLT

SPD

LOOP

SCAN

TIME

(P.019) = 10

MS

0.00 to 327.67

RAD

/

S

when

FEEDBACK

SELECT

(P.200)

ARMATURE

VOLT

SPD

LOOP

SCAN

TIME

(P.019) = 5

MS

Default Setting:

3.00

RAD

/

S

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) - Speed/Voltage Loop

(

SPD

) Tuning

A setting of 0.00 allows proportional-only speed loop control.

This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.

SPD

LOOP

PI

PROP

GAIN

(P.211)

Speed loop PI block
proportional gain.

Parameter Range:

0.10 to 128.00

Default Setting:

4.40

Parameter Type:

Tunable

OIM Menu Path(s):

Speed/Voltage Loop (

SPD

) - Speed/Voltage Loop

(

SPD

) - Tuning

This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.

SPD

LOOP

PI

RESET

While this is

ON

, the

speed loop

PI

block is

held in reset and the
block’s output is the
initial value selected
by

SPD

LOOP

PI

INIT

VAL

(Drop_1, register

39 of the alternate
network register
map).

Parameter Range:

0 =

OFF

1 =

ON

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

This parameter is only available over the network. It
cannot be viewed through the

OIM

.

SPD

LOOP

PI

RESET

is forced

OFF

when

CONTROL

SOURCE

SELECT

is not

NETWORK

.

Refer to the appropriate network communication manual for register map
assignments.