Configuring the Speed Reference

4-5

ANLG

AUTO

GAIN

ADJ

(P.101)

Scales the analog
auto reference signal
after it is conditioned
by the drive
hardware.

Parameter Range:

0.750 to 1.250

Default Setting:

1.000

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling

Typically, this parameter is set to 1.000.

Example

If

ANLG

AUTO

SIGNAL

TYPE

(P.100) is set to 0 -10V, a 0 to 8.2VDC signal produces

only 82% of the drive’s full scale value. To produce the drive’s full scale value,

change

ANLG

AUTO

GAIN

ADJ

to properly scale the signal to 1.22

.

Important: Adjust the zero point (

ANLG

AUTO

ZERO

ADJ

(P.102)) before setting the

gain adjust.

ANLG

AUTO

SIGNAL

TYPE

(P.100)

Selects the type of
signal applied to the
drive analog auto
reference input. This
is the signal at
terminals 19 and 20
on the Regulator
board.

Parameter Range:

0– 10V
+/–10V
4-20 mA
10-50mA

Default Setting:

0– 10V

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Important: Jumpers J10 and J12 must be set for the type of analog auto reference

selected. See the hardware manual for instruction.

ANLG

AUTO

ZERO

ADJ

(P.102)

Removes any offset
from the analog auto
reference signal.

Parameter Range:

–200 to 200

Default Setting:

0

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling

If

ANALOG

AUTO

REFERENCE

(P.188) is not equal to zero when the analog auto

reference signal is set to its minimum value (for example, 0 volts or 4mA), adjust

ANLG

AUTO

ZERO

ADJ

up or down until

ANALOG

AUTO

REFERENCE

(P.188) equals zero.

10

8.2

--------

1.22

=