P.428), P.013) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 46

Advertising
background image

4-26

FlexPak 3000 DC Drive Software Reference

DIG

IN

0

SELECT

(P.428)

Determines which
function is controlled
by digital input 0
(terminal 12 on the
Regulator board).

Parameter Range:

1 =

BRUSH

WEAR

INPUT

2 =

JOG

SPEED

SELECT

3 =

OCL

ENABLE

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters (listed by parameter number)

The functions can be:

BRUSH

WEAR

: The input is from a brush wear indicator. If the input is

OFF

, the

MOTOR

BRUSH

WEAR

LOW

alarm is generated. You must have the E.S.P. Brush

Monitor Detector kit installed to use this option.

JOG

SPEED

SELECT

: The input determines whether

JOG

SPEED

1 (P.012) or

JOG

SPEED

2 (P.017) will be used when the drive is jogging.

OCL

ENABLE

: Enables the outer control loop if

CONTROL

SOURCE

SELECT

is not set

to

NETWORK

and if the I/O Expansion kit is not installed. If an I/O Expansion kit is

installed, the outer control loop enable signal is digital input 5. See section 9.1 for
information.

JOG

ACCEL

/

DECEL

TIME

(P.013)

Sets the minimum
time that the jog
reference can change
from zero to

TOP

SPEED

(P.011) and

from

TOP

SPEED

to

zero.

Parameter Range:

0.1 to 300.0 seconds

Default Setting:

3.0 seconds

Parameter Type:

Tunable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp
Quick Start

The

S

-

CURVE

ROUNDING

parameter does not affect the setting of this parameter.