FlexPak 3000 DC Drive Software Reference

4.1.3 Configuring the Analog Manual Reference

CONTROL

SOURCE

SELECT

must be set to

TERMBLK

to use the analog manual reference

input as a speed reference. This reference can only be used when the drive is
configured as a speed regulator and

MANUAL

REF

SELECT

(P.106) is set to

ANALOG

.

When you use this speed reference, the drive uses the analog manual reference from
terminals 16(+10V), 17(+), and 18(–) of the Regulator board.

The software uses the parameters described in this section to scale the analog
manual reference signal at terminal 16, 17, and 18 to produce the

ANALOG

MAN

REFERENCE

(P.192) signal.

The analog manual reference input can also be used for the trim reference. Make sure
they are not being used for both functions at the same time.

AUTO

REFERENCE

SELECT

(P.103)

AUTO

REFERENCE

SELECT

determines if

the drive uses a
frequency or analog
input reference
source when the
drive is in

AUTO

mode

and

CONTROL

SOURCE

SELECT

is set to

KEYPAD

,

TERMBLK

, or

SERIAL

.

Parameter Range:

ANALOG

FREQUENCY

IN

Default Setting:

ANALOG

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

When

AUTO

REFERENCE

SELECT

is set to

FREQUENCY

IN

, the reference is from the

frequency input (terminals 39, 40, and 41 on the I/O Expansion kit).

When

AUTO

REFERENCE

SELECT

is set to

ANALOG

, the reference is from the analog

auto input (terminals 19 and 20 on the Regulator board).

If the I/O Expansion kit is not installed, this parameter is automatically configured to

ANALOG

and cannot be changed.

ANALOG

MAN

REFERENCE

(P.192)

The analog reference
value in manual
mode. This is the
value output by the
drive after all
hardware and
software scaling.

Parameter Range:

n/a

Default Setting:

n/a

Parameter Type:

Output

OIM Menu Path(s):

Drive Reference - Drive Reference Scaling
Drive Reference - Drive Reference Test Points

This parameter is only used when the drive is configured as a speed/voltage
regulator.