1 configuration for all networks, P.901) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual

Page 108

Advertising
background image

10-2

FlexPak 3000 DC Drive Software Reference

10.1 Configuration for All Networks

NETW

COMM

LOSS

SELECT

(P.901)

Selects how the drive
will respond to
network
communication loss
when

CONTROL

SOURCE

SELECT

is set

to

NETWORK

.

Parameter Range:

FAULT

USE

LAST

REF

USE

TRMBLK

REF

4 =

USE

TRMBLK

CNTL

Default Setting:

FAULT

Parameter Type:

Tunable

OIM Menu Path(s):

Network Communications

The choices are:

FAULT

: A fault is generated when network communication is lost, causing the drive

to coast/DB stop.

USE

LAST

REF

: The drive continues to run if network communication is lost, using

the last reference value received over the network. The alarm A00004,

NETWORK

COMMUNICATION

TIMEOUT

, is generated if network communication is lost.

USE

TRMBLK

REF

: The drive continues to run if network communication is lost,

using the selected auto reference value from the Regulator board terminal strip
(terminals 19 and 20). The drive automatically switches back to the network
reference when network communication is re-established. The alarm A00004,

NETWORK

COMMUNICATION

TIMEOUT

, is generated if network communication is lost.

4 (

USE

TRMBLK

CNTL

): The drive continues to run if network communication is lost.

The Regulator board terminal strip will become the source for all control (Run,
Jog, Stop, Fault Reset, Direction, and OCL Enable) and speed (auto) reference
signals. The Speed Loop PI Reset and Underwind/Overwind bits cannot be
changed while operating in this mode. They will remain at the last values received
from the network. The drive automatically switches back to the network reference
and control when network communication is re-established. Alarm A00004,

NETWORK

COMMUNICATION

TIMEOUT

, is generated if network communication is lost.

This selection is available only when the ControlNet Network Communication
board is installed in the drive.

Alarms do not cause the drive to stop. Therefore, some form of hardwired stop must
be available in case of network communication loss, since stopping the drive
through the network might not be possible. Once the drive is stopped, it cannot be
restarted until network communication is re-established or

CONTROL

SOURCE

SELECT

is changed to something other than

NETWORK

.

If

CONTROL

SOURCE

SELECT

is not set to

NETWORK

, the loss of network

communication does not affect operation of the drive.

Important: The stop button on the

OIM

is aways functional, regardless of the vlaue

of this parameter.

!

ATTENTION: When

USE

TRMBLK

REF

or

USE

TRMBLK

CNTL

are selected,

motor speed and direction changes can occur when network
communication is lost and restored. All terminal block reference and
control signals must be set to correct values for your application. Failure
to observe this precaution could result in damage to, or destruction of,
equipment.

Advertising