Out (output), Function, Bitnum is the i/o point in the module from 1 to 4 – Yaskawa LEGEND-MC User Manual

Page 190

Advertising
background image

180

LEGEND-MC User’s Manual

@OUT (Output)

[Function]

DESCRIPTION:

@OUT returns the status of the digital output number or variable given in square brackets. Note that the
@OUT command is a function, which means that it does not follow the convention of the commands, and
does not require the underscore when used as an operand.

ARGUMENTS: @OUT [n]

where

n is an integer corresponding to a specific output on the controller. The first output on the controller is
denoted as output 1. A LEGEND-MC controller has 4 digital outputs plus applicable I/O connected by
Modbus.

NOTE: When using Modbus devices, the I/O points of the modbus devices are calculated using the

following formula:

n = (SlaveAddress*1000) + (HandleNum*1000) + ((Module-1)*4) + (Bitnum-1)

Slave Address is used when the ModBus device has slave devices connected to it and specified as
Addresses 0 to 255. Please note that the use of slave devices for modbus are very rare and this number will
usually be 0.

HandleNum is the handle specifier from A to P (1 - 16).

Module is the position of the module in the rack from 1 to 16.

BitNum is the I/O point in the module from 1 to 4.

USAGE:

EXAMPLES:

NOTE: @OUT only returns the output state of local controller.

While Moving

Yes

Minimum n value

1

In a Program

Yes

Maximum n value

8

Not in a program

Yes

Default Value

---

Can be Interrogated

No

Default Format

---

Used as an Operand

Yes

Distributed Control

No, Local

#TEST

Program TEST

VAR1=3

Set variable

MG @OUT[VAR1]

Display only the whole number portion of
VAR1

EN

End of program

Advertising