Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual

Page 274

Advertising
background image

PLC Designer V2.x| Lenze Application Samples

The L_S8S_Drive82SMD.lib library

L_S8S_ActuatorSpeed - actuation of the 8400 SMD controller

274

L

1.3 EN - 07/2012

15.1.2

Structure S8S_DriveStatus - status of the controller

The bit assignment in the software application is identical to the bit assignment in the

controller.

Identifier/data type

Control bits in the controller

Bit

Identifier

Meaning

FreeBit00

0

Not assigned

FreeBit01

1

Not assigned

FreeBit02

2

Not assigned

FreeBit03

3

Not assigned

FreeBit04

4

Not assigned

xQmin

BOOL

5

DCTRL1-NOUT=0

Frequency threshold Qmin

xFreeBit06

6

Not assigned

xDriveEnabled

BOOL

7

DCTRL1-CINH

TRUE: Controller active

xDriveError

BOOL

8

Status for error in the controller

TRUE: Error in the controller reported

FALSE: No error reported

xFreeBit09

9

Not assigned

xFreeBit10

10

Not assigned

xFreeBit11

11

Not assigned

xFreeBit12

12

Not assigned

xFreeBit13

13

Not assigned

xCwCcw

BOOL

14

Mapping of C0417/15

Define direction of rotation of the motor

• TRUE: CW rotation active (clockwise)

• FALSE: CCW rotation active (counter-

clockwise)

xDriveReady

BOOL

15

Mapping of C0417/16

Status of the CAN node setting

rNact

REAL

Actual speed value