2 l_scb_canstatus - node inspection, Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual

Page 284

Advertising
background image

PLC Designer V2.x| Lenze Application Samples

The L_SCB_CANBasic.lib library

L_SCB_CanStatus - node inspection

284

L

1.3 EN - 07/2012

17.2

L_SCB_CanStatus - node inspection

This program creates a status overview of the nodes. Incorrect nodes can be detected and

restarted.

Inputs

Note!

Only one of the two FBs (either L_SCB_CanStatus or L_SCB_StatusSingleNode)

can be used at a time!
• The simultaneous use of the two FBs causes a time-out (xPDOTimeOut).

Identifier/data type

Information/possible settings

tPdoTimeOut

TIME

100 ms (Lenze setting)

xAutomaticReset

BOOL

TRUE: Activate automatic restart

tResetTime

TIME

10 s (Lenze setting)

Note!

When using the visualisation template for the L_SCB_CanStatus FB, please

observe that the visualisation page does not automatically update the status

messages.
• Remedy: Click on the visualisation page or reload the visualisation window

(by switching to another window for a little while) to update the display of

the status messages.