10 l_scb_parwrite - write parameter, L_scb_parwrite - write parameter, Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual

Page 291

Advertising
background image

1.3 EN - 07/2012

L

291

PLC Designer V2.x| Lenze Application Samples

The L_SCB_CANBasic.lib library

L_SCB_ParWrite - write parameter

17.10

L_SCB_ParWrite - write parameter

This FB writes the value of data input dwData to a parameter.

Outputs

Identifier/data type

Information/possible settings

xExecute

BOOL

Trigger write request.

TRUE Start write request once.

FALSE Deactivate writing.

byNodeNumber

BYTE

Node number

xUseSecondSDO

BOOL

TRUE: Use second SDO channel

byMasterNumber

BYTE

Interface number (0...3)

wIndex

WORD

CANopen index (0x0 ... 0xFFFF).

bySubCode

BYTE

Subcode (0 ... 255)

dwData

DWORD

Parameter value to be written

byNrOfBYTE

BYTE

Number of bytes (initial value: 4)

Identifier/data type

Information/possible settings

xDone

BOOL

TRUE: Read request completed

xBusy

BOOL

Status output "Read request sent"

• TRUE: The read request was sent to the operating system and the FB is waiting for

a response from the device addressed.

• FALSE: The read request was completed.

xError

BOOL

Status output "Error"

• TRUE: During the processing an error has occurred.

xTimeOut

BOOL

Signalling of a time-out (time-out error)

• TRUE: Time-out; read request could not be executed

• FALSE: No time-out detected