Setting the polarity of digital inputs and outputs, Commissioning – Lenze ECSCAxxx User Manual

Page 129

Advertising
background image

Commissioning

Setting the polarity of digital inputs and outputs

6

l

129

EDBCSXA064 EN 3.2

6.9

Setting the polarity of digital inputs and outputs

The polarity can be set for each digital input and output. This determines whether the
input or output is HIGH active or LOW active.

The following are available:

ƒ

4 digital inputs (X6/DI1 ... DI4)

ƒ

1 digital output (X6/DO1)

ƒ

1 relay output (X25/BD1, BD2)

The GDC contains codes for setting the polarity of digital inputs and outputs in the
parameter menu under Terminal I/O:

Fig. 6−7

GDC view: Setting of the polarity of digital inputs and outputs

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0114

Polarity of the digital inputs

^ 129

1 DIGIN pol

0

HIGH level active

X6/DI1 (DIGIN_bIn1_b)

2 DIGIN pol

0

HIGH level active

X6/DI2 (DIGIN_bIn2_b)

3 DIGIN pol

0

HIGH level active

X6/DI3 (DIGIN_bIn3_b)

4 DIGIN pol

0

HIGH level active

X6/DI4 (DIGIN_bIn4_b)

0

HIGH level active

1

LOW level active

C0118

Polarity of the digital outputs

^ 345

^ 129

1 DIGOUT pol

0

HIGH level active

X6/DO1 (DIGOUT_bOut1_b)

2 DIGOUT pol

0

HIGH level active

X25 (DIGOUT_bRelais_b, brake
connection)

0

HIGH level active

1

LOW level active